Requires a plugin version later than 9.1.008. Up to 9.1.008,
OnOffOnTimeDelayandOnOffOffWaitTimeonly wrote an attribute once (see 2.1).
A relay that Domoticz switches On is normally switched Off by Domoticz too. If Domoticz, the plugin or the Zigbee network goes down in between, the relay stays On. For an irrigation valve, a pump or a heater that is a real risk.
The On/Off cluster lets the device run that timer itself: On With Timed Off
(cluster 0x0006, command 0x42). The plugin sends it with every On when the
device Param OnOffOnTimeDelay is set.
Tuya relays implement the same command differently, and the plugin handles them
through a flag in the device configuration (TuyaOnOffCountdown).
| ZCL compliant device | Tuya countdown device | |
|---|---|---|
Does 0x42 switch the relay On? |
Yes | No |
| Unit of OnTime | 1/10 s | seconds |
| When the time is up | switches Off | toggles the relay |
| Plugin sends | 0x42 alone |
On, then 0x42 |
| Enabled by | Param OnOffOnTimeDelay |
same Param + device conf TuyaOnOffCountdown |
Zigbee Cluster Library (ZCL, document 07-5123), section 3.8, On/Off cluster. The timed-off feature comes from the lighting profile (ZLL) and is optional: many relays do not implement it.
| Id | Name | Type | Meaning |
|---|---|---|---|
0x0000 |
OnOff | bool | current state |
0x4001 |
OnTime | uint16, 1/10 s | time left before the device switches itself Off |
0x4002 |
OffWaitTime | uint16, 1/10 s | time left during which On With Timed Off cannot switch the device On |
0xFFFF in OnTime or OffWaitTime means “do not count down”, so the longest real
value is 0xFFFE (6553.4 s, about 1 h 49 min).
0x42 On With Timed Off| Field | Type | Meaning |
|---|---|---|
| OnOffControl | map8 | bit 0 Accept Only When On: when set, the command is ignored if the device is Off |
| OnTime | uint16, 1/10 s | how long to stay On |
| OffWaitTime | uint16, 1/10 s | guard time, see below |
Example, 10 minutes On, no guard, the payload after the ZCL header:
42 00 70 17 00 00
│ │ └───┴─ OnTime 6000 = 0x1770, little endian
│ └─ OnOffControl 0x00
└─ command 0x42 OffWaitTime 0 ─┘
OnTime and OffWaitTime are not settings: they are the countdown itself.
| Event | Effect |
|---|---|
| Every 1/10 s, device On, OnTime > 0 | OnTime − 1. At 0: OffWaitTime = 0 and the device switches Off |
| Every 1/10 s, device Off, OffWaitTime > 0 | OffWaitTime − 1 |
| On | switches On. If OnTime = 0, OffWaitTime = 0. A running countdown continues |
| Off | switches Off and OnTime = 0. OffWaitTime is kept: the guard starts |
| Toggle | acts as Off or On |
0x42, device On |
OnTime = the longer of the current and the new value; OffWaitTime = new value |
0x42, device Off, OffWaitTime = 0 |
switches On, OnTime and OffWaitTime = new values |
0x42, device Off, OffWaitTime > 0 |
stays Off (guard); OffWaitTime = the shorter of the two |
Write OnTime (0x4001) |
starts the countdown if the device is On, or at the next On |
Consequences:
0x42. To stop
earlier, send Off.0x42, not a plain On.0x4001 gives at most one timed cycle. A timer on
every On means sending the values with every On, which is what 0x42 does.The table follows the CSA reference implementation of the same cluster
(OnOffLightingCluster.cpp in the Matter SDK, whose comments quote the ZCL
text); see the references.
Two device Params, set in Device Management (see Device parameters):
| Param | Unit | Meaning |
|---|---|---|
OnOffOnTimeDelay |
seconds | auto-off delay sent with every On. 0 or unset = plain On |
OnOffOffWaitTime |
seconds | guard time sent with it (ZCL devices only). Usually 0 |
Each takes one value for every endpoint, or one value per endpoint:
'OnOffOnTimeDelay': 900
'OnOffOnTimeDelay': {'01': 1500, '02': 900, '03': 1200, '04': 600}
The plugin converts to each device’s unit: × 10 for the ZCL fields, capped at
0xFFFE (6553 s, about 1 h 49 min); whole seconds for a Tuya countdown,
capped at 43200 (12 h). Changing a Param writes nothing to the device: the
values are only used when an On is sent.
Until this change,
OnOffOnTimeDelayandOnOffOffWaitTimewrote their value as is into the attributes0x4001/0x4002, once, when the Param changed. The unit was not documented and depended on the device (1/10 s on a ZCL device, seconds on a Tuya countdown), and as shown in 1.3 the write only covered the next On.OnOffOnTimeDelayreached0x4001only from release 9.1.007 (#2064), and no certified device configuration declares these Params, so only users who set them by hand see the new behaviour.
Domoticz On
└─ Modules/actuators.py actuator_on()
└─ Modules/onoff_settings.py onoff_on_with_timed_off()
├─ OnOffOnTimeDelay unset for this endpoint → returns False → plain On
├─ native ZiGate (no raw mode) → error logged, returns False → plain On
├─ device conf TuyaOnOffCountdown → On, then 0x42 in seconds
└─ otherwise → 0x42 (OnTime, OffWaitTime) × 10, in 1/10 s
└─ Zigbee/zclCommands.py zcl_onoff_on_with_timed_off()
└─ Zigbee/zclRawCommands.py raw_zcl_zcl_onoff(…, "OnWithTimedOff")
raw_zcl_zcl_onoff() builds the 0x42 payload: OnOffControl 0x00, then
OnTime and OffWaitTime as little endian uint16.0x42. On a native ZiGate the
plugin logs an error and sends a plain On, so the device still switches On.actuator_on(): group commands, Toggle,
set-level with on/off on dimmers, and devices driven through Tuya datapoints
(TS0601).Many Tuya relays and plugs (TS0001 to TS0004, TS011F…) use command 0x42
for their countdown feature, in a way that departs from the ZCL:
0x42 does not switch the relay On. It only starts a countdown.0x4001), in seconds, every 60 s.zigbee-herdsman-converters (Zigbee2MQTT) implements exactly this in
tuya.on_off_countdown: send the state first, then onWithTimedOff with
ontime = offwaittime = countdown. Many Tuya device definitions there enable
it with onOffCountdown: true.
What goes wrong with the standard sequence: sending 0x42 alone (the ZCL
way) to a Tuya relay that is Off does not switch it On, and when the countdown
ends the relay switches On by itself. Observed on a TS0004
_TZ3000_u3oupgdy (MHCOZY TYWB 4ch-RF): the relay did not switch On, and the
Domoticz widget fell back to Off. With the Tuya sequence below, the same relay
switches On and then Off by itself after the delay.
How the plugin handles it: with "TuyaOnOffCountdown": true in the device
configuration (see Device configuration attributes),
onoff_on_with_timed_off() sends:
0x42 with OnTime = OffWaitTime = OnOffOnTimeDelay in seconds, rounded
up to a whole second and capped at 43200 (12 h).OnOffOffWaitTime is ignored for these devices.
The flag belongs in the device configuration, not in a user Param: the
behaviour depends on the model and firmware, a wrong choice is unsafe, and
Tuya devices driven through datapoints (TS0601) work differently again.
With a lamp on the relay, not a valve:
'OnOffOnTimeDelay': 60 (60 s).zclCommand debug log
on, check that the only frames sent are the expected ones.| What happens | Meaning | Next |
|---|---|---|
| On at once, Off after 60 s | ZCL behaviour works | keep it |
| Stays Off | Tuya countdown, or 0x42 not supported |
add TuyaOnOffCountdown to its device configuration (a copy in Conf/Local-Devices, see Model name resolution) and test again |
| On, stays On after 60 s | device ignores 0x42 |
remove the Param; this device has no device-side auto-off |
In the “stays Off” case with a Tuya device, the countdown has started: the lamp switches On at the end of it. Send an Off to cancel.
OnOffLightingCluster.cpp:
HandleOn, HandleOff, HandleOnWithTimedOff, TimerFired.zigpy.zcl.clusters.general.OnOff: attributes
on_time 0x4001, off_wait_time 0x4002; command on_with_timed_off
0x42 with on_off_control (bit Accept_Only_When_On = 1), on_time,
off_wait_time (uint16).src/lib/tuya.ts,
on_off_countdown (toZigbee and fromZigbee).