ZigBeeForDomoticZ plugin Wiki

Device-side auto-off: On With Timed Off

Requires a plugin version later than 9.1.008. Up to 9.1.008, OnOffOnTimeDelay and OnOffOffWaitTime only wrote an attribute once (see 2.1).

A relay that Domoticz switches On is normally switched Off by Domoticz too. If Domoticz, the plugin or the Zigbee network goes down in between, the relay stays On. For an irrigation valve, a pump or a heater that is a real risk.

The On/Off cluster lets the device run that timer itself: On With Timed Off (cluster 0x0006, command 0x42). The plugin sends it with every On when the device Param OnOffOnTimeDelay is set.

Tuya relays implement the same command differently, and the plugin handles them through a flag in the device configuration (TuyaOnOffCountdown).

  ZCL compliant device Tuya countdown device
Does 0x42 switch the relay On? Yes No
Unit of OnTime 1/10 s seconds
When the time is up switches Off toggles the relay
Plugin sends 0x42 alone On, then 0x42
Enabled by Param OnOffOnTimeDelay same Param + device conf TuyaOnOffCountdown

1. What the Zigbee specification says

Zigbee Cluster Library (ZCL, document 07-5123), section 3.8, On/Off cluster. The timed-off feature comes from the lighting profile (ZLL) and is optional: many relays do not implement it.

1.1 Attributes

Id Name Type Meaning
0x0000 OnOff bool current state
0x4001 OnTime uint16, 1/10 s time left before the device switches itself Off
0x4002 OffWaitTime uint16, 1/10 s time left during which On With Timed Off cannot switch the device On

0xFFFF in OnTime or OffWaitTime means “do not count down”, so the longest real value is 0xFFFE (6553.4 s, about 1 h 49 min).

1.2 Command 0x42 On With Timed Off

Field Type Meaning
OnOffControl map8 bit 0 Accept Only When On: when set, the command is ignored if the device is Off
OnTime uint16, 1/10 s how long to stay On
OffWaitTime uint16, 1/10 s guard time, see below

Example, 10 minutes On, no guard, the payload after the ZCL header:

42 00 70 17 00 00
│  │  └───┴─ OnTime 6000 = 0x1770, little endian
│  └─ OnOffControl 0x00
└─ command 0x42          OffWaitTime 0 ─┘

1.3 Behaviour

OnTime and OffWaitTime are not settings: they are the countdown itself.

Event Effect
Every 1/10 s, device On, OnTime > 0 OnTime − 1. At 0: OffWaitTime = 0 and the device switches Off
Every 1/10 s, device Off, OffWaitTime > 0 OffWaitTime − 1
On switches On. If OnTime = 0, OffWaitTime = 0. A running countdown continues
Off switches Off and OnTime = 0. OffWaitTime is kept: the guard starts
Toggle acts as Off or On
0x42, device On OnTime = the longer of the current and the new value; OffWaitTime = new value
0x42, device Off, OffWaitTime = 0 switches On, OnTime and OffWaitTime = new values
0x42, device Off, OffWaitTime > 0 stays Off (guard); OffWaitTime = the shorter of the two
Write OnTime (0x4001) starts the countdown if the device is On, or at the next On

Consequences:

The table follows the CSA reference implementation of the same cluster (OnOffLightingCluster.cpp in the Matter SDK, whose comments quote the ZCL text); see the references.


2. How the plugin implements it

2.1 Configuration

Two device Params, set in Device Management (see Device parameters):

Param Unit Meaning
OnOffOnTimeDelay seconds auto-off delay sent with every On. 0 or unset = plain On
OnOffOffWaitTime seconds guard time sent with it (ZCL devices only). Usually 0

Each takes one value for every endpoint, or one value per endpoint:

'OnOffOnTimeDelay': 900
'OnOffOnTimeDelay': {'01': 1500, '02': 900, '03': 1200, '04': 600}

The plugin converts to each device’s unit: × 10 for the ZCL fields, capped at 0xFFFE (6553 s, about 1 h 49 min); whole seconds for a Tuya countdown, capped at 43200 (12 h). Changing a Param writes nothing to the device: the values are only used when an On is sent.

Until this change, OnOffOnTimeDelay and OnOffOffWaitTime wrote their value as is into the attributes 0x4001 / 0x4002, once, when the Param changed. The unit was not documented and depended on the device (1/10 s on a ZCL device, seconds on a Tuya countdown), and as shown in 1.3 the write only covered the next On. OnOffOnTimeDelay reached 0x4001 only from release 9.1.007 (#2064), and no certified device configuration declares these Params, so only users who set them by hand see the new behaviour.

2.2 Flow

Domoticz On
 └─ Modules/actuators.py      actuator_on()
     └─ Modules/onoff_settings.py  onoff_on_with_timed_off()
         ├─ OnOffOnTimeDelay unset for this endpoint  → returns False → plain On
         ├─ native ZiGate (no raw mode)               → error logged, returns False → plain On
         ├─ device conf TuyaOnOffCountdown            → On, then 0x42 in seconds
         └─ otherwise                                 → 0x42 (OnTime, OffWaitTime) × 10, in 1/10 s
             └─ Zigbee/zclCommands.py     zcl_onoff_on_with_timed_off()
                 └─ Zigbee/zclRawCommands.py raw_zcl_zcl_onoff(…, "OnWithTimedOff")

2.3 Not covered


3. What is specific to Tuya

Many Tuya relays and plugs (TS0001 to TS0004, TS011F…) use command 0x42 for their countdown feature, in a way that departs from the ZCL:

zigbee-herdsman-converters (Zigbee2MQTT) implements exactly this in tuya.on_off_countdown: send the state first, then onWithTimedOff with ontime = offwaittime = countdown. Many Tuya device definitions there enable it with onOffCountdown: true.

What goes wrong with the standard sequence: sending 0x42 alone (the ZCL way) to a Tuya relay that is Off does not switch it On, and when the countdown ends the relay switches On by itself. Observed on a TS0004 _TZ3000_u3oupgdy (MHCOZY TYWB 4ch-RF): the relay did not switch On, and the Domoticz widget fell back to Off. With the Tuya sequence below, the same relay switches On and then Off by itself after the delay.

How the plugin handles it: with "TuyaOnOffCountdown": true in the device configuration (see Device configuration attributes), onoff_on_with_timed_off() sends:

  1. a plain On;
  2. 0x42 with OnTime = OffWaitTime = OnOffOnTimeDelay in seconds, rounded up to a whole second and capped at 43200 (12 h).

OnOffOffWaitTime is ignored for these devices.

The flag belongs in the device configuration, not in a user Param: the behaviour depends on the model and firmware, a wrong choice is unsafe, and Tuya devices driven through datapoints (TS0601) work differently again.


4. Checking a device on the bench

With a lamp on the relay, not a valve:

  1. Set 'OnOffOnTimeDelay': 60 (60 s).
  2. Make sure no Off Delay or script in Domoticz switches it Off.
  3. Switch it On from Domoticz and touch nothing. With the zclCommand debug log on, check that the only frames sent are the expected ones.
What happens Meaning Next
On at once, Off after 60 s ZCL behaviour works keep it
Stays Off Tuya countdown, or 0x42 not supported add TuyaOnOffCountdown to its device configuration (a copy in Conf/Local-Devices, see Model name resolution) and test again
On, stays On after 60 s device ignores 0x42 remove the Param; this device has no device-side auto-off

In the “stays Off” case with a Tuya device, the countdown has started: the lamp switches On at the end of it. Send an Off to cancel.